Motor
Starters PKZM0
Whether type
"1" or type "2" coordination, PKZM0 motor starter
combinations with DILM contactors for up to 4 kW/400V control short-circuit
currents up to 100kA. There is no need for upstream protective devices.
The IEC/EN
60947 standard classifies motor starters according to type "1"
and type "2" coordination. This specifies the response of the
motor starters under short-circuit conditions.
Both coordination
types ensure the safe disconnection of the short-circuit. The only difference
is the state of the motor starter after the short circuit has occurred.
Motor starters complying with type "1" coordination are inexpensive
starters for standard applications. The standard allows the starter to
be damaged by short circuits.
In the case
of motor starters including a PKZM0, only the contactor needs to be checked,
since PKZM0 motor-protective circuit-breakers always comply with type
"2" coordination.
A PKZM0 motor-protective
circuit-breaker with a DILM contactor provides coordination type "1"
or "2", depending on the combination. The commonest applications
can thus be covered with just a few standard components, resulting in
major stockholding advantages.
|